کليد اتوماتیک اشنایدر
Circuit breaker Compact NSX400F, 36 kA at 415 VAC, Micrologic 5.3 A trip unit 400 A, 3 poles 3d
range |
Compact
|
|
---|---|---|
product name |
Compact NSX
|
|
device short name |
Compact NSX400F
|
|
product or component type |
Circuit breaker
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
[In] rated current |
400 A at 40 °C
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
suitability for isolation |
Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2 |
|
utilisation category |
Category A
|
|
[Icu] rated ultimate short-circuit breaking capacity |
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 240 V AC 50/60 Hz conforming to UL 508 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 20 kA at 600 V AC 50/60 Hz conforming to UL 508 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Performance level |
F 36 kA 415 V AC
|
|
trip unit name |
Micrologic 5.3 A
|
|
trip unit technology |
Electronic
|
|
trip unit protection functions |
LSI
|
|
control type |
Toggle
|
|
Circuit breaker mounting mode |
Fixed
|
[Ui] rated insulation voltage |
800 V AC 50/60 Hz
|
|
---|---|---|
[Uimp] rated impulse withstand voltage |
8 kV
|
|
[Ics] rated service short-circuit breaking capacity |
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
mechanical durability |
15000 cycles
|
|
electrical durability |
12000 cycles 440 V In/2 conforming to IEC 60947-2
3000 cycles 690 V In conforming to IEC 60947-2 6000 cycles 440 V In conforming to IEC 60947-2 6000 cycles 690 V In/2 conforming to IEC 60947-2 |
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
connection pitch |
45 mm
|
|
protection type |
L : for overload protection (long time)
S : for short time short-circuit protection I : for instantaneous short-circuit protection |
|
trip unit rating |
400 A at 40 °C
|
|
Long-time pick-up adjustment type Ir (thermal protection) |
Adjustable
|
|
[Ir] long-time protection pick-up adjustment range |
100…400 A
|
|
Long-time protection delay adjustment type tr |
Adjustable
|
|
[tr] long-time protection delay adjustment range |
15…400 s at 1.5 x Ir
0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir |