توضیحات
circuit breaker Masterpact NW10H1 – 1000 A – 3 poles – drawout – w/o trip unit
48245
کليد هوایی 1000 آمپر سه پل کشویی سری NW قدرت قطع 65kA
NW10H13P2AD
میکرولوجیک 2
واحد حفاظتی Micrologic
حفاظت جریان
- حفاظت پایه ای: Micrologic 2
- نوع حفاظت: زمان طولانی + آنی
- حفاظت انتخابی: Micrologic 5 Selective
- نوع حفاظت: زمان طولانی + زمان کوتاه + آنی
range of product |
Masterpact NW
|
|
---|---|---|
product or component type |
Basic frame
|
|
device short name |
Masterpact NW10
|
|
circuit breaker name |
Masterpact NW10H1
|
|
poles description |
3P
|
|
network type |
AC
|
|
breaking capacity code |
H1
|
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category B
|
network frequency |
50/60 Hz
|
|
---|---|---|
control type |
Push-button
|
|
mounting mode |
Drawout
|
|
[In] rated current |
1000 A at 40 °C
|
|
[Ui] rated insulation voltage |
1000 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
12 kV conforming to IEC 60947-2
|
|
[Icm] rated short-circuit making capacity |
143 kA 525 V AC at 50/60 Hz
143 kA 690 V AC at 50/60 Hz |
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
circuit breaker CT rating |
1000 A
|
|
breaking capacity |
65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
protection type |
Without protection
|
|
mechanical durability |
12500 cycles without maintenance conforming to IEC 60947-2
25000 cycles with maintenance conforming to IEC 60947-2 |
|
electrical durability |
10000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
10000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-23A: 10000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
|
connection pitch |
115 mm
|
|
[Icw] rated short-time withstand current |
36 kA 3 s conforming to IEC 60947-2
65 kA 1 s conforming to IEC 60947-2 |
|
maximum breaking time |
25 ms
|
|
maximum closing response time |
70 ms
|
|
height |
439 mm
|
|
width |
441 mm
|
|
depth |
394.5 mm
|
standards |
IEC 60947-2
|
|
---|---|---|
product certifications |
ASTA
|
|
pollution degree |
4 conforming to IEC 60664-1
|
|
ambient air temperature for operation |
-25…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|