توضیحات
کليد هوایی اشنایدر الکتریک 1600 آمپر سه پل کشویی سری NT قدرت قطع 42kA
47240 –کليد هوایی 1600 آمپر سه پل کشویی سری NT قدرت قطع 42kA
NT16H13P2EF –میکرولوجیک 2
circuit breaker Masterpact NT16H1 – 1600 A – 3 poles – drawout – w/o trip unit
range of product |
Masterpact NT
|
|
---|---|---|
product or component type |
Basic frame
|
|
device short name |
Masterpact NT16
|
|
circuit breaker name |
Masterpact NT16H1
|
|
poles description |
3P
|
|
network type |
AC
|
|
breaking capacity code |
H1
|
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category B
|
network frequency |
50/60 Hz
|
|
---|---|---|
control type |
Push-button
|
|
mounting mode |
Drawout
|
|
[In] rated current |
1600 A at 40 °C
|
|
[Ui] rated insulation voltage |
1000 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
12 kV conforming to IEC 60947-2
|
|
[Icm] rated short-circuit making capacity |
88 kA 220/415 V AC at 50/60 Hz
88 kA 440 V AC at 50/60 Hz 88 kA 525 V AC at 50/60 Hz 88 kA 690 V AC at 50/60 Hz |
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
circuit breaker CT rating |
1600 A
|
|
breaking capacity |
42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
protection type |
Without protection
|
|
mechanical durability |
12500 cycles without maintenance conforming to IEC 60947-2
|
|
electrical durability |
3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
|
connection pitch |
70 mm
|
|
[Icw] rated short-time withstand current |
24 kA 3 s conforming to IEC 60947-2
42 kA 0.5 s conforming to IEC 60947-2 42 kA 1 s conforming to IEC 60947-2 |
|
maximum breaking time |
25 ms
|
|
maximum closing response time |
50 ms
|
|
height |
322 mm
|
|
width |
288 mm
|
|
depth |
276.5 mm
|
standards |
IEC 60947-2
|
|
---|---|---|
product certifications |
LCIE
ASEFA |
|
pollution degree |
3 conforming to IEC 60664-1
|
|
ambient air temperature for operation |
-25…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
Sustainable offer status |
Green Premium product
|
|
---|---|---|
EU RoHS Directive |
Compliant
EU RoHS Declaration |
|
Mercury free |
Yes
|
|
RoHS exemption information |
Yes
|
|
China RoHS Regulation |
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information |
|
Environmental Disclosure |
Product Environmental Profile
|
|
Circularity Profile |
End of Life Information
|
Warranty |
18 months
|
---|